Solar Inverters
GES48160M300-500XP · 16,000W · 120/240Vac split-phase · 51.2V battery · Dual MPPT
| Model | GES48160M300-500XP |
| Rated Output | 16,000W model rating — split-phase system |
| AC Output | 120/240Vac · split-phase · L1+L2+N+PE |
| Nominal Battery Voltage | 51.2Vdc (48V-class system) |
| Maximum PV input power | 12,000W + 12,000W = 24,000W |
| Maximum PV input voltage | 500V |
| PV input / MPPT voltage range | 90–450V |
| Maximum MPPT input current | 36A + 36A |
| Maximum PV charging current | 300A |
| AC input voltage range, per phase | 85–140Vac |
| AC input frequency range | 47–55Hz / 57–65Hz |
| Maximum AC input current, per phase | 90Aac |
| Maximum AC charging current | 200Adc |
| Maximum battery charge / discharge current | 300A / 340A |
| Maximum efficiency, battery to load | >93.5% |
| Grid breaker rating | 100A |
| Dimensions (datasheet order) | 720 × 482 × 149mm |
| Weight | 37.5kg |
| Communication ports | USB / RS485 / WiFi / CAN |
| AC coupling | Yes; configuration and local interconnection requirements apply |
| Display | Colour touch screen |
| Output rating clarification | Confirm allowable load per 120V leg and imbalance limits in writing; the supplied sheet uses ambiguous per-phase / same-phase labels. |
| PV start voltage | 120V |
| MPPT channels | 2 |
| Output frequency | 50/60Hz |
| Power factor | 1 |
| Minimum battery start voltage | 44V |
| Battery operating / charge voltage range | 40–60Vdc |
| Battery types | Lead-acid / lithium; charging settings and BMS compatibility must be confirmed |
| Grid overload protection | Circuit breaker |
| Battery short-circuit protection | Fuse |
| AC reverse-feed protection | Yes — CT configuration and installation requirements apply |
| AC output short-circuit / wiring protection | Yes |
| Transfer time | 10ms typical; critical-load suitability requires system assessment |
| Operating temperature | −10°C to 55°C; derating above 45°C |
| Storage temperature | −25°C to 60°C |
| Humidity range | 5%–95% |
| Cooling | Forced-air cooling, variable speed |
| Protection class | IP21 — indoor installation |
| Noise | ≤60dB |
| Altitude | 4,000m maximum; no derating at or below 2,000m |
| Parallel units | 1 to 6; approved model combinations, firmware and wiring required |
| Dry-contact generator control | Yes |
| Battery-less operation | Yes — solar + grid operating mode |
| Remote diagnostics / OTA | Listed in supplied datasheet; confirm enabled configuration |
| CT anti-backflow | Yes; not a substitute for utility interconnection approval |
| Warranty | 2 years; applicable warranty terms govern |
Send model, quantity, target country, battery requirements and branding files for a wholesale or OEM quotation. Lithium battery compatibility and destination approvals require a model-specific review.
Confirm export packing dimensions, gross weight, included accessories and shipping terms in the quotation. Inverter warranty: 2 years under the applicable warranty policy.
FAQ
GES48160M300-500XP supplies 120/240Vac split-phase service with L1, L2, neutral and protective earth. A 120V single-phase inverter supplies one line and neutral. Match the site service and load distribution before selecting a model.
Do not assume so. This model lists 340A continuous battery discharge. Confirm bank voltage, aggregate continuous current, BMS communication, cabling and protection. A battery peak-current figure alone does not establish continuous power compatibility.
The supplied datasheet lists two MPPT channels at 12,000W and 36A per channel, 24,000W total. Maximum PV voltage is 500V and the tracking range is 90–450V. Check cold-weather string open-circuit voltage and channel current.
The supplied datasheet lists up to six units. Six times 16kW equals 96kW aggregate nominal power, subject to approved wiring, compatible firmware, battery current and site design.
Do not infer this from the headline model rating. The supplied sheet has ambiguous per-phase and same-phase labels. Request written confirmation of per-leg power, allowable imbalance and the intended wiring arrangement before design approval.
No. These are operating functions. Obtain the exact model certificate and confirm local electrical and utility requirements before any grid-connected installation or export arrangement.
Download the supplied GES48160M300-500XP PDF on this page. Send the destination, quantity, load list, AC service, PV design and battery specification to info@patternbattery.com or use the enquiry form.
Related Products
Solar Inverters
SPI4865M150-300P 6.5kW 120V hybrid inverter: 48V battery, 9kW dual MPPT, up to 6 parallel units. View specifications and download the PDF.
Solar Inverters
PATTERN SPI2436M120-500: 3,600W residential hybrid inverter with 120Vac single-phase output, 24V-class battery input and up to 6,000W PV input.
Solar Inverters
PATTERN SPI4836M80-300P: 3,600W residential hybrid inverter with 120Vac single-phase output, 48V battery input and up to 6,000W PV input.
Solar Inverters
PATTERN PT-TM1512 low-frequency solar inverter for off-grid and backup power projects. See the model datasheet for electrical specifications.

Reliable products, factory supply and technical support for local distributors and installers.
Become Our Distributor