EN
PATTERN
PATTERN PTF12-100 12V 100Ah front terminal battery front view

Lead Acid Batteries

12V 100Ah Front Terminal Battery (PTF12-100)

Front-access terminals for cabinet wiring and service. Compare the 100Ah model by dimensions, discharge duration and charging settings before specifying a backup battery bank.

PTF12-100 · 12V 100Ah front terminal
  • Front-access terminal layout for connection and inspection in battery cabinets.
  • T3 terminals with an ABS container.
  • Standby charging voltage: 13.5–13.8V at 25°C.
  • Model-specific PDF includes constant-current and constant-power discharge tables.
  • Wholesale and OEM/ODM enquiries: specify quantity, cabinet space and destination market.

Technical Specifications

ModelPTF12-100
Nominal Voltage12V
Nominal Capacity100Ah
10-Hour Rated Capacity100Ah at 10A, 1.80V/cell, 25°C (datasheet discharge rating)
Length508 ± 2mm
Width110 ± 1.5mm
Total Height238.5 ± 2mm
Approximate Weight31.0kg
TerminalT3
Container MaterialABS
Internal ResistanceApprox. 4.5mΩ
Maximum Discharge Current (5 seconds)1000A — short-duration rating, not continuous current
Cycle Charge Voltage (25°C)14.1–14.4V
Initial Cycle Charge CurrentLess than 30A
Standby Charge Voltage (25°C)13.5–13.8V
Operating Temperature — Discharge−15 to 50°C
Operating Temperature — Charge0 to 40°C
Storage Temperature−15 to 40°C
Storage / Refresh ChargeUp to 6 months at 25°C before a freshening charge; shorter intervals at higher temperatures.

Applications

  • ·Telecom and communications backup cabinets
  • ·UPS and standby power supplies
  • ·Solar backup projects with a correctly configured charger

OEM / ODM & Packaging

Send the required voltage, capacity, order quantity, target country and private-label requirements for a distributor or OEM/ODM quotation.

Request model-specific packing dimensions, shipping weight and transport documents before confirming an order.

FAQ

12V 100Ah Front Terminal Battery (PTF12-100) — Frequently Asked Questions

Is this a lithium battery?

No. PTF12-100 is listed in the PATTERN front terminal lead-acid battery range. Use its own charging parameters; do not apply LiFePO4 charging settings.

Does the maximum discharge rating describe continuous current?

No. The 1000A figure is a 5-second rating. Use the PDF constant-current or constant-power tables for the required backup duration and final voltage.

Which charging voltage should I use?

The PTF12-100 datasheet lists 14.1–14.4V for cycle use and 13.5–13.8V for standby use at 25°C. Temperature compensation and current limits must follow the model datasheet.

Where can I download the specifications?

Use Download PDF Datasheet on this page for the original PTF12-100 specification, dimensions and discharge curves.

Related Products

You May Also Need

PATTERN PT75-12 12V 75Ah Deep Cycle AGM Battery

Lead Acid Batteries

12V 75Ah Deep Cycle AGM Battery

PATTERN PT75-12 12V 75Ah deep cycle AGM lead-acid battery. View product photos and request wholesale supply.

PATTERN PT65-12 12V 65Ah Deep Cycle AGM Battery

Lead Acid Batteries

12V 65Ah Deep Cycle AGM Battery

PATTERN PT65-12 12V 65Ah deep cycle AGM lead-acid battery. View product photos and request wholesale supply.

PATTERN PT7-6 6V 7Ah Deep Cycle AGM Battery

Lead Acid Batteries

6V 7Ah Deep Cycle AGM Battery

PATTERN PT7-6 6V 7Ah deep cycle AGM lead-acid battery. View product photos and request wholesale supply.

PATTERN PT14-6 6V 14Ah Deep Cycle AGM Battery

Lead Acid Batteries

6V 14Ah Deep Cycle AGM Battery

PATTERN PT14-6 6V 14Ah deep cycle AGM lead-acid battery. View product photos and request wholesale supply.

PATTERN Is Looking for Home Energy Storage Distributors Worldwide

Reliable products, factory supply and technical support for local distributors and installers.

Become Our Distributor
WhatsApp Us Call Get Quote Factory direct · Reply within 4 working hours · English support