Solar Inverters
SPI4865M150-300P · 6,500W · 120Vac single-phase · 48V battery · Dual MPPT
| Model | SPI4865M150-300P |
| Rated Output | 6,500W |
| Maximum AC output apparent power | 6,500VA |
| Peak output / duration | 9,750VA / 5s |
| AC Output | 120Vac · single-phase · L+N+PE |
| Nominal Battery Voltage | 48Vdc |
| Maximum PV input power | 4,500W + 4,500W = 9,000W |
| Maximum PV input voltage | 300V |
| PV input voltage range | 90–300V |
| MPPT voltage range | 90–280V |
| Maximum MPPT input current | 22A per channel (two channels) |
| Maximum PV charging current | 150A — PV charging figure; maximum battery charge current is separately listed as 120A |
| AC input voltage range | 85–140Vac |
| AC input frequency range | 47–55Hz / 57–65Hz |
| Maximum AC input current | 60Aac |
| Maximum AC charging current | 120Adc |
| Maximum battery charge / discharge current | 120A / 135A |
| Maximum efficiency, battery to load | >92% |
| Grid breaker rating | 63A |
| Dimensions (datasheet order) | 540 × 380 × 120mm |
| Weight | 18kg |
| Communication ports | USB / RS485 / WiFi |
| PV start voltage | 120V |
| MPPT channels | 2 |
| Output frequency | 50/60Hz |
| Power factor | 1 |
| Minimum battery start voltage | 44V |
| Battery operating / charge voltage range | 40–60Vdc |
| Battery types | Lead-acid / lithium; charging settings and BMS compatibility must be confirmed |
| Grid overload protection | Circuit breaker |
| Battery short-circuit protection | Fuse |
| AC reverse-feed protection | Yes — CT configuration and installation requirements apply |
| AC output short-circuit / wiring protection | Yes |
| Transfer time | 10ms typical; critical-load suitability requires system assessment |
| Operating temperature | −10°C to 55°C; derating above 45°C |
| Storage temperature | −25°C to 60°C |
| Humidity range | 5%–95% |
| Cooling | Forced-air cooling, variable speed |
| Protection class | IP21 — indoor installation |
| Noise | ≤60dB |
| Altitude | 4,000m maximum; no derating at or below 2,000m |
| Parallel units | 1 to 6; approved model combinations, firmware and wiring required |
| Dry-contact generator control | Yes |
| Battery-less operation | Yes — solar + grid operating mode |
| Remote diagnostics / OTA | Listed in supplied datasheet; confirm enabled configuration |
| CT anti-backflow | Yes; not a substitute for utility interconnection approval |
| Warranty | 2 years; applicable warranty terms govern |
Send model, quantity, target country, battery requirements and branding files for a wholesale or OEM quotation. Lithium battery compatibility and destination approvals require a model-specific review.
Confirm export packing dimensions, gross weight, included accessories and shipping terms in the quotation. Inverter warranty: 2 years under the applicable warranty policy.
FAQ
One SPI4865M150-300P provides 120Vac single-phase output. A split-phase or three-phase arrangement requires the manufacturer-approved multi-unit configuration; do not assume a single unit provides 240V.
Use a compatible 48V-class bank within the 40–60Vdc operating window. Check charging settings, BMS protocol and aggregate continuous discharge capability against the 135A model rating, with the required design margin.
No. PV input is 4,500W per MPPT channel, 9,000W total. Rated AC output remains 6,500W. PV open-circuit voltage and channel current must stay within the model limits.
The supplied datasheet lists one to six units. Confirm firmware, connection accessories, AC arrangement, protection and battery-bank design before ordering a parallel system.
The datasheet lists solar + grid battery-less operation. Backup performance without a battery depends on available sources and the selected operating mode; it is not guaranteed autonomous backup.
The supplied datasheet lists safety and EMC references. Obtain the exact model certificate, regional approvals and utility acceptance before a grid-connected installation; a specification sheet alone is not proof of approval.
Use Download PDF Datasheet on this page. Send SPI4865M150-300P, quantity, destination, intended AC arrangement and battery details through the enquiry form or email info@patternbattery.com.
Related Products
Solar Inverters
GES48160M300-500XP 16kW 120/240V split-phase hybrid inverter: 24kW dual MPPT, 300A charge and 340A discharge. View specs and download the PDF.
Solar Inverters
PATTERN SPI2436M120-500: 3,600W residential hybrid inverter with 120Vac single-phase output, 24V-class battery input and up to 6,000W PV input.
Solar Inverters
PATTERN SPI4836M80-300P: 3,600W residential hybrid inverter with 120Vac single-phase output, 48V battery input and up to 6,000W PV input.
Solar Inverters
PATTERN PT-TM1512 low-frequency solar inverter for off-grid and backup power projects. See the model datasheet for electrical specifications.

Reliable products, factory supply and technical support for local distributors and installers.
Become Our Distributor